CONSTRUCTION:
18 ga. steel cabinet with
powder coated finish and control compartment housing a master terminal board
with a hinged and latched access door, simplifying wiring, installation &
maintenance. Product Companies -
Markel and Raywall
HEATING ELEMENT:
Spiral fin steel element
with continuously brazed steel fins formed to allow side draw through air flow.
OVERHEAT PROTECTION:
All units come equipped
with automatic reset type limit to de-energize the heater should an over-temperature
situation occur.
FAN and MOTOR:
Totally enclosed,
1-speed 1-phase, permanently lubricated, thermally protected motors with unit
bearings on 3 KW - 20 KW models.
Totally enclosed, 2-speed, 1-phase, permanently lubricated, thermally
protected motors with sleeve bearings on 25 KW - 50 KW models.
Fan over-ride purges unit of residual heat at shutdown
LOUVER ASSEMBLY:
Louvers are individually
adjustable for directional control of air flow up to 15° from straight horizontal
Optional difusers available for down flow (vertical discharge) applications
TEMPERATURE CONTROLS:
Units with model
numbers ending in CA1 are factory wired for low voltage controls
25 KW through 50 KW units are designed for two stage heating operation
INTSTALLATION:
Unit Heaters can
be mounted for horizontal or vertical discharge
5100 Series suggested for applications up to 6,000 feet.
9' RECOMMENDED MOUNTING HEIGHT
Control Voltage - 208
|
208
VOLT
|
| TYPE
=
Wall / Ceiling |
VOLT
= 208 |
TEMP.
RISE = 26°F |
| AIR THROW
= 12'
|
CFM = 400 |
BTU'S
= 11,262 |
| PHASE
= 1/3 |
AMPS = 15.9
/ 9.2 |
WEIGHT (lbs)
= 25 |
| MOTOR
ENCLOSURE
=TE |
KW = 3.3
|
WARRANTY = 1
yr. limited |
DIMENSIONS:
- A = 17 3/4"
- B = 14 15/32"
- C = 6 1/2"